In Section 9.6 of the Air Force Stress Analysis Manual, an example is provided for an axially loaded lug. The male lug strength, female lug strength, and double shear joint strength are calculated. This validation case follows the Air Force example to ensure consistent results between the Air Force Manual and MechaniCalc's Lug Analysis calculator.

Male Lugs and Bushings

The inputs for the male lug, per the input table, are specified below:

Geometry:

D = 1 in hole diameter
e = 1.5 in edge distance (hole center to edge of lug)
a = 1 in distance (edge of hole to edge of lug)
w = 3 in width
t2 = 0.75 in thickness

Material Properties:  7075-T651 Plate

Sty = 66,000 psi tensile yield strength
Stu = 77,000 psi tensile ultimate strength
E = 10.3 x 106 psi elastic modulus
εu = 0.06 ultimate strain

Comparison Summary

A summary of the male lug results calculated in the Air Force Manual versus those calculated in MechaniCalc's Lug Analysis calculator is provided below. It can be seen that the results are essentially equivalent. Any differences are due to slight variations in determining the \(K\) coefficients from the charts, or are due to rounding errors.

Air Force Manual MechaniCalc Lug Calculator
Lug Bearing Strength 77,000 lbf 77,060 lbf
Lug Net-Section Tension Strength 100,485 lbf 101,466 lbf
Bushing Bearing Strength 44,000 lbf 44,010 lbf
Combined Lug-Bushing Design Strength 44,000 lbf 44,010 lbf

Lug Bearing Strength

The male lug bearing strength as calculated in the Air Force Manual is:

Male Lug Bearing Strength

The results from the Lug Analysis calculator are shown below. The predicted bearing strength is just slightly below that calculated in the Air Force Manual (28,440 lbf vs. 28,600 lbf) due to a slightly lower \( K_{axial} \) value read off of the figure (1.45 vs. 1.46). The strength values are within 0.56%.

Axial Load Coefficient

Male Lug Bearing Strength

Lug Net-Section Tension Strength

The male lug net-section tension strength as calculated in the Air Force Manual is:

Male Lug Net-Section Tension Strength

NOTE:  The final equation above is incorrect, and the corrected value is \(P_{nu.L} = 100,485 \text{ lbf} \). A full explanation is given below.


In the equation for \(P_{nu.L}\) above, the incorrect equation was used (9-6b vs. 9-6a). The relevant equations from the Air Force Manual are shown below:

Net-Section Strength Equations

If \( F_{tu} \le 1.304 F_{ty} \), then Equation 9-6a should be used, otherwise Equation 9-6b should be used.

\( F_{tu} = 77000 \text{ psi} \)
\( 1.304 F_{ty} = 86100 \text{ psi} \)
\( F_{tu} \lt 1.304 F_{ty} \)

Since in this case \( F_{tu} \lt 1.304 F_{ty} \), Equation 9-6a should be used. Although the solution in the example stated that Equation 9-6a was used, in reality 9-6b was used. The correction for the example is:

$$ \begin{eqnarray} P_{nu.L} &=& F_{nu.L} (w-D) t \\ &=& K_n F_{tu} (w-D) t \\ &=& 0.87 \cdot 77000 \cdot (3.0 - 1.0) \cdot 0.75 \\ &=& 100,485 \text{ lbf} \end{eqnarray} $$

The results from the Lug Analysis calculator are shown below:

Male Lug Net-Section Tension Stress Coefficient

Male Lug Net-Section Tension Strength

Lug Design Strength

The male lug design strength as calculated in the Air Force Manual is:

Male Lug Design Strength

MechaniCalc's Lug Analysis calculator does not determine a design strength until the bushing bearing strength has also been calculated (in the next step).

Bushing Bearing Strength

The male bushing bearing strength as calculated in the Air Force Manual is:

Male Bushing Bearing Strength

The results from the Lug Analysis calculator are shown below. The predicted bearing strength is equivalent to the value calculated in the Air Force Manual (with the only differences being attributable to rounding on the part of the Air Force Manual):

Male Lug Bushing Bearing Strength

Combined Lug-Bushing Design Strength

The combined male lug-bushing design strength as calculated in the Air Force Manual is:

Male Combined Design Strength

The results from the Lug Analysis calculator are shown below. The predicted strength is equivalent to the value calculated in the Air Force Manual:

Male Lug Combined Design Strength